CARBOMET GAS ANALYSIS
CARBOmet series CO2 analysers use a cell based on non-dispersive infrared technology.
The basic functions meet every type of application requirement and include:
– Microprocessor control
– Analysis display on a 4-digit LED display
– 2 fully user-configurable set-points with relay output
– Audible alarm
– Linear 4…20 mA output
– RS 232 serial output (standard) or RS 485 (optional), ModBus RTU protocol
– Programming using three buttons on the front panel
– Adjustable Zero and Span calibration using dedicated commands in the device menu.
Applications
Process monitoring for air analysis control in greenhouses
Process monitoring for air analysis control in hyperbaric chambers
Air monitoring in modified atmospheres for food packaging
Process monitoring in industry and laboratories
Technical Data
Power supply: 220 Vac, 50/60 Hz, P max 10 VA, 0.5 A fuse
Measuring range: 0…30%, 0…100%, CO2
Visual indication: No. 4 red 7-segment displays
Alarm set-point 1: red LED Ø 5 mm
Alarm set-point 2: red LED Ø 5 mm
Audible indication: max. 95 dB at 1 metre
Output: 4…20 mA, common negative, maximum load 700 Ohm, minimum open-circuit voltage 15 Vdc
Response time: < 60 seconds from 10 to 90% F.S.
Initial warm-up: 4 minutes
Combined error: < ±3% F.S.
Long-term drift: < 1% F.S. over 12 months
Ambient temperature correction: cell thermostatically controlled at 40°C
Operating humidity: 0/99% RH, non-condensing
Sample flow rate: 0.7-12 l/min
Pneumatic connections: 1/8″ F
External enclosure: black aluminium, DIN 43700, dimensions 96 x 96 x (d) 169 mm
Communication port: local ModBus network interface, unidirectional RS 232
Weight: 1,600 g
Operating temperature: 0…50°C
Certifications and reference standards: CE
Contacts
Techno Gas Equipment s.r.l.
Strada Privata delle Valli, 10
24040 Suisio (BG)
CF 02476750969
P.IVA IT02092130984
REA BG 318553
Codice SDI USAL8PV
© 2026 T.G.E. Techno Gas Equipment S.r.l. | Privacy Policy | Cookie Policy